POWER QUALITY phần 8

pdf
Số trang POWER QUALITY phần 8 20 Cỡ tệp POWER QUALITY phần 8 3 MB Lượt tải POWER QUALITY phần 8 0 Lượt đọc POWER QUALITY phần 8 44
Đánh giá POWER QUALITY phần 8
4.9 ( 11 lượt)
Nhấn vào bên dưới để tải tài liệu
Đang xem trước 10 trên tổng 20 trang, để tải xuống xem đầy đủ hãy nhấn vào bên trên
Chủ đề liên quan

Nội dung

6 Power Factor 6.1 INTRODUCTION Power factor is included in the discussion of power quality for several reasons. Power factor is a power quality issue in that low power factor can sometimes cause equipment to fail. In many instances, the cost of low power factor can be high; utilities penalize facilities that have low power factor because they find it difficult to meet the resulting demands for electrical energy. The study of power quality is about optimizing the performance of the power system at the lowest possible operating cost. Power factor is definitely an issue that qualifies on both counts. 6.2 ACTIVE AND REACTIVE POWER Several different definitions and expressions can be applied to the term power factor, most of which are probably correct. Apparent power (S) in an electrical system can be defined as being equal to voltage times current: S = V × I(1Ø) S = 3 × V × I ( 3∅ ) where V = phase-to-phase voltage (V) and I = line current (VA). Power factor (PF) may be viewed as the percentage of the total apparent power that is converted to real or useful power. Thus, active power (P) can be defined by: P = V × I × PF – 1Ø P = 3 × V × I × PF – 3∅ In an electrical system, if the power factor is 0.80, 80% of the apparent power is converted into useful work. Apparent power is what the transformer that serves a home or business has to carry in order for that home or business to function. Active power is the portion of the apparent power that performs useful work and supplies losses in the electrical equipment that are associated with doing the work. Higher power factor leads to more optimum use of electrical current in a facility. Can a power factor reach 100%? In theory it can, but in practice it cannot without some form of power factor correction device. The reason why it can approach 100% power factor but not quite reach it is because all electrical circuits have inductance and capacitance, which introduce reactive power requirements. The reactive power is that © 2002 by CRC Press LLC P = ACTIVE POWER Q = REACTIVE POWER S = TOTAL (OR APPARENT) POWER P POWER FACTOR ANGLE Q S FIGURE 6.1 Power triangle and relationship among active, reactive, and apparent power. portion of the apparent power that prevents it from obtaining a power factor of 100% and is the power that an AC electrical system requires in order to perform useful work in the system. Reactive power sets up a magnetic field in the motor so that a torque is produced. It is also the power that sets up a magnetic field in a transformer core allowing transfer of power from the primary to the secondary windings. All reactive power requirements are not necessary in every situation. Any electrical circuit or device when subjected to an electrical potential develops a magnetic field that represents the inductance of the circuit or the device. As current flows in the circuit, the inductance produces a voltage that tends to oppose the current. This effect, known as Lenz’s law, produces a voltage drop in the circuit that represents a loss in the circuit. At any rate, inductance in AC circuits is present whether it is needed or not. In an electrical circuit, the apparent and reactive powers are represented by the power triangle shown in Figure 6.1. The following relationships apply: 2 S = P +Q 2 (6.1) P = S cosØ (6.2) Q = S sinØ (6.3) Q/P = tanØ (6.4) where S = apparent power, P = active power, Q = reactive power, and Ø is the power factor angle. In Figure 6.2, V is the voltage applied to a circuit and I is the current in the circuit. In an inductive circuit, the current lags the voltage by angle Ø, as shown in the figure, and Ø is called the power factor angle. If XL is the inductive reactance given by: XL = 2πfL then total impedance (Z ) is given by: Z = R + jXL where j is the imaginary operator = © 2002 by CRC Press LLC –1 R V I V I L FIGURE 6.2 Voltage, current, and power factor angle in a resistive/inductive circuit. The power factor angle is calculated from the expression: tanØ = (XL/R) or Ø = tan–1(XL/R) (6.5) Example: What is the power factor of a resistive/inductive circuit characterized by R = 2 Ω, L = 2.0 mH, f = 60 Hz? XL = 2πfL = 2 × π × 60 × 2 × 10–3 = 0.754 Ω tanØ = XL/R = 0.754/2 = 0.377 Ø = 20.66° Power factor = PF = cos(20.66) = 0.936 Example: What is the power factor of a resistance/capacitance circuit when R = 10 Ω, C = 100 µF, and frequency (f) = 60 Hz? Here, XC = 1/2πfC = 1/2 × π × 60 × 100 × 10–6 = 26.54 Ω tanØ = (–XC/R) = –2.654 Ø = –69.35° Power factor = PF = cosØ = 0.353 The negative power factor angle indicates that the current leads the voltage by 69.35°. Let’s now consider an inductive circuit where application of voltage V produces current I as shown in Figure 6.2 and the phasor diagram for a single-phase circuit is as shown. The current is divided into active and reactive components, IP and IQ: © 2002 by CRC Press LLC IP = I × cosØ IQ = I × sinØ Active power = P = V × active current = V × I × cosØ Reactive power = Q = V × reactive current = V × I × Ø Total or apparent power = S = 2 2 (P + Q ) = 2 2 2 2 2 2 ( V I cos ∅ + V I sin ∅ ) = V × I Voltage, current, and power phasors are as shown in Figure 6.3. Depending on the reactive power component, the current phasor can swing, as shown in Figure 6.4. The ±90° current phasor displacement is the theoretical limit for purely inductive and capacitive loads with zero resistance, a condition that does not really exist in practice. V P P = VI COS Q = VI SIN IQ IP I S= S Q FIGURE 6.3 Relationship among voltage, current, and power phasors. I C CURRENT LEADS VOLTAGE V I I L FIGURE 6.4 Theoretical limits of current. © 2002 by CRC Press LLC CURRENT LAGS VOLTAGE P 2 + 2 Q 6.3 DISPLACEMENT AND TRUE POWER FACTOR The terms displacement and true power factor, are widely mentioned in power factor studies. Displacement power factor is the cosine of the angle between the fundamental voltage and current waveforms. The fundamental waveforms are by definition pure sinusoids. But, if the waveform distortion is due to harmonics (which is very often the case), the power factor angles are different than what would be for the fundamental waves alone. The presence of harmonics introduces additional phase shift between the voltage and the current. True power factor is calculated as the ratio between the total active power used in a circuit (including harmonics) and the total apparent power (including harmonics) supplied from the source: True power factor = total active power/total apparent power Utility penalties are based on the true power factor of a facility. 6.4 POWER FACTOR IMPROVEMENT Two ways to improve the power factor and minimize the apparent power drawn from the power source are: • Reduce the lagging reactive current demand of the loads • Compensate for the lagging reactive current by supplying leading reactive current to the power system The second method is the topic of interest in this chapter. Lagging reactive current represent the inductance of the power system and power system components. As observed earlier, lagging reactive current demand may not be totally eliminated but may be reduced by using power system devices or components designed to operate with low reactive current requirements. Practically no devices in a typical power system require leading reactive current to function; therefore, in order to produce leading currents certain devices must be inserted in a power system. These devices are referred to as power factor correction equipment. 6.5 POWER FACTOR CORRECTION In simple terms, power factor correction means reduction of lagging reactive power (Q) or lagging reactive current (IQ). Consider Figure 6.5. The source V supplies the resistive/inductive load with impedance (Z): Z = R + jωL I = V/Z = V/(R + jωL) Apparent power = S = V × I = V2/(R + jωL) © 2002 by CRC Press LLC LEADING Q R P V XL=wL= 2 fL S LAGGING Q FIGURE 6.5 Lagging and leading reactive power representation. Multiplying the numerator and the denominator by (R – jωL), S = V2(R – jωL)/(R2 + ω2L2) Separating the terms, S = V2R/(R2 + ω2L2) – jV2ωL/(R2 + ω2L2) S = P – jQ (6.6) The –Q indicates that the reactive power is lagging. By supplying a leading reactive power equal to Q, we can correct the power factor to unity. From Eq. (6.4), Q/P = tanØ. From Eq. (6.5), Q/P = ωL/R = tanØ and Ø = tan–1 (ωL/R), thus: Power factor = cosØ = cos (tan–1ωL/R) (6.7) Example: In the circuit shown in Figure 6.5, V = 480 V, R = 1 Ω, and L = 1 mH; therefore, XL = ωL = 2πfL = 2π × 60 × .001 = 0.377 Ω From Eq. (6.6), Active power = P = V2R/(R2 + ω2L2) = 201.75 kW Reactive power = Q = V2ωL/(R2 + ω2L2) = 76.06 kVAR Power factor angle = Ø = tan–1 (Q/P) = tan–1(0.377) = 20.66° Power factor = PF = cosØ = 0.936 The leading reactive power necessary to correct the power factor to 1.0 is 76.06 kVAR. © 2002 by CRC Press LLC 20.66 DEG. 11.48 DEG. V=480 V P = 201.75 KW Q2 = 40.97 KVAR 35.09 LEADING KVARS NEEDED TO INCREASE PF FROM 0.936 TO 0.98 Q1 = 76.06 KVAR FIGURE 6.6 Power factor correction triangle. In the same example, what is the leading kVAR required to correct the power factor to 0.98? At 0.98 power factor lag, the lagging kVAR permitted can be calculated from the following: Power factor angle at 0.98 = 11.48° tan(11.48°) = Q/201.75 = 0.203 Q = 0.203 × 201.75 = 40.97 kVAR The leading kVAR required in order to correct the power factor to 0.98 = 76.06 – 40.97 = 35.09 (see Figure 6.6). In a typical power system, power factor calculations, values of resistance, and inductance data are not really available. What is available is total active and reactive power. From this, the kVAR necessary to correct the power factor from a given value to another desired value can be calculated. Figure 6.7 shows the general power factor correction triangles. To solve this triangle, three pieces of information are needed: existing power factor (cosØ1), corrected power factor (cosØ2), and any one of the following: active power (P), reactive power (Q), or apparent power (S). • Given P, cosØ1, and cosØ2: From the above, Q1 = PtanØ1 and Q2 = PtanØ2. The reactive power required to correct the power factor from cosØ1 to cosØ2 is: ∆Q = P(tanØ1 – tanØ2) • Given S1, cosØ1, and cosØ2: From the above, Q1 = S1sinØ1, P = S1cosØ1, and Q2 = PtanØ2. The leading reactive power necessary is: ∆Q = Q1 – Q2 © 2002 by CRC Press LLC • Given Q1, cosØ1, and cosØ2: From the above, P = Q1/tanØ1 and Q2 = PtanØ2. The leading reactive power necessary is: ∆Q = Q1 – Q2 Example: A 5-MVA transformer is loaded to 4.5 MVA at a power factor of 0.82 lag. Calculate the leading kVAR necessary to correct the power factor to 0.95 lag. If the transformer has a rated conductor loss equal to 1.0% of the transformer rating, calculate the energy saved assuming 24-hour operation at the operating load. Figure 6.8 contains the power triangle of the given load and power factor conditions: Existing power factor angle = Ø1 = cos–1(0.82) = 34.9° Corrected power factor angle = Ø2 = cos–1(0.95) = 18.2° Q1 = S1sinØ1 = 4.5 × 0.572 = 2.574 MVAR P = S1cosØ1 = 4.5 × 0.82 = 3.69 MW Q2 = PtanØ2 = 3.69 × 0.329 = 1.214 MVAR 1 2 P S2 Q2 S1 Q Q1 FIGURE 6.7 General power factor correction triangle. © 2002 by CRC Press LLC The leading MVAR necessary to improve the power factor from 0.82 to 0.95 = Q1 – Q2 = 1.362. For a transformer load with improved power factor S2: S2 = 2 2 ( P + Q 2 ) = 3.885 MVA The change in transformer conductor loss = 1.0 [(4.5/5)2 – (3.885/5)2] = 0.206 p.u. of rated losses, thus the total energy saved = 0.206 × 50 × 24 = 247.2 kWhr/day. At a cost of $0.05/kWhr, the energy saved per year = 247.2 × 365 × 0.05 = $4511.40. 6.6 POWER FACTOR PENALTY Typically, electrical utilities charge a penalty for power factors below 0.95. The method of calculating the penalty depends on the utility. In some cases, the formula is simple, but in other cases the formula for the power factor penalty can be much more complex. Let’s assume that one utility charges a rate of 0.20¢/kVAR–hr for all the reactive energy used if the power factor falls below 0.95. No kVar–hr charges are levied if the power factor is above 0.95. In the example above, at 0.82 power factor the total kVar–hr of reactive power used per month = 2574 × 24 × 30. The total power factor penalty incurred each month = 2574 × 24 × 30 × 0.20 × 0.01 = $3707. The cost of having a low power factor per year is $44,484. The cost of purchasing and installing power factor correction equipment in this specific case would be about $75,000. It is not difficult to see the cost savings involved by correcting the power factor to prevent utility penalties. 1 = 34.9 DEG. 2 = 18.2 DEG. P = 3.69 MW S2 = 3.885 MVA Q2 = 1.214 MVAR S1 = 4.5 MVA Q = 1.362 MVAR Q1 = 2.574 MVAR FIGURE 6.8 Power factor triangle for Section 6.4 example. © 2002 by CRC Press LLC Another utility calculates the penalty using a different formula. First, kW demand is increased by a factor equal to the 0.95 divided by actual power factor. The difference between this and the actual demand is charged at a rate of $3.50/kW. In the example, the calculated demand due to low power factor = 3690 × 0.95/0.82 = $4275, thus the penalty kW = 4275 – 3690 = $585, and the penalty each month = 585 × $3.50 = $2047. In this example, the maximum demand is assumed to be equal to the average demand calculated for the period. The actual demand is typically higher than the average demand. The penalty for having a poor power factor will be correspondingly higher. In the future, as the demand for electrical power continues to grow, the penalty for poor power factors is expected to get worse. 6.7 OTHER ADVANTAGES OF POWER FACTOR CORRECTION Correcting low power factor has other benefits besides avoiding penalties imposed by the utilities. Other advantages of improving the power factor include: • • • • • Reduced heating in equipment Increased equipment life Reduction in energy losses and operating costs Freeing up available energy Reduction of voltage drop in the electrical system In Figure 6.9, the total apparent power saved due to power factor correction = 4500 – 3885 = 615 kVA, which will be available to supply other plant loads or help minimize capital costs in case of future plant expansion. As current drawn from the source is lowered, the voltage drop in the power system is also reduced. This is important in large industrial facilities or high-rise commercial buildings, which are typically prone to excessive voltage sags. 6.8 VOLTAGE RISE DUE TO CAPACITANCE When large power factor correction capacitors are present in an electrical system, the flow of capacitive current through the power system impedance can actually R IC XL I C XL V1 IC C V2 I CR = V1 I CR I C X L V1 I CR V2 I C XL V2 >V 1 V2 FIGURE 6.9 Schematic and phasor diagram showing voltage rise due to capacitive current flowing through line impedance. © 2002 by CRC Press LLC
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.