Số trang Karady, George G. “Transmission System” The Electric Power Engineering Handbook Ed. L.L. Grigsby 104 Cỡ tệp Karady, George G. “Transmission System” The Electric Power Engineering Handbook Ed. L.L. Grigsby 4 MB Lượt tải Karady, George G. “Transmission System” The Electric Power Engineering Handbook Ed. L.L. Grigsby 0 Lượt đọc Karady, George G. “Transmission System” The Electric Power Engineering Handbook Ed. L.L. Grigsby 0
Đánh giá Karady, George G. “Transmission System” The Electric Power Engineering Handbook Ed. L.L. Grigsby
4.1 ( 14 lượt)
Nhấn vào bên dưới để tải tài liệu
Đang xem trước 10 trên tổng 104 trang, để tải xuống xem đầy đủ hãy nhấn vào bên trên
Chủ đề liên quan

Nội dung

Karady, George G. “Transmission System” The Electric Power Engineering Handbook Ed. L.L. Grigsby Boca Raton: CRC Press LLC, 2001 © 2001 CRC Press LLC 4 Transmission System George G. Karady Arizona State University 4.1 Concept of Energy Transmission and Distribution 4.2 Transmission Line Structures George G. Karady Joe C. Pohlman 4.3 Insulators and Accessories George G. Karady and R.G. Farmer 4.4 Transmission Line Construction and Maintenance Wilford Caulkins and Kristine Buchholz 4.5 Insulated Power Cables for High-Voltage Applications Carlos V. Núñez-Noriega and Felimón Hernandez 4.6 Transmission Line Parameters Manuel Reta-Hernández 4.7 Sag and Tension of Conductor D.A. Douglass and Ridley Thrash 4.8 Corona and Noise Giao N. Trinh 4.9 Geomagnetic Disturbances and Impacts upon Power System Operation John G. Kappenman 4.10 Lightning Protection William A. Chisholm 4.11 Reactive Power Compensation Rao S. Thallam © 2001 CRC Press LLC 4 Transmission System 4.1 Concept of Energy Transmission and Distribution Generation Stations • Switchgear • Control Devices • Concept of Energy Transmission and Distribution 4.2 Traditional Line Design Practice • Current Deterministic Design Practice • Improved Design Approaches George G. Karady Arizona State University 4.3 Consultant Arizona State University 4.4 Wilford Caulkins 4.5 4.6 Glendale Community College Felimón Hernandez 4.7 Arizona State University 4.8 Southwire Company Log-In John G. Kappenman Metatech Corporation William A. Chisholm Ontario Hydro Technologies Rao S. Thallam Salt River Project © 2001 CRC Press LLC Corona and Noise Corona Modes • Main Effects of Discharges on Overhead Lines • Impact on the Selection of Line Conductors • Conclusions Ridley Thrash Giao N. Trinh Sag and Tension of Conductor Catenary Cables • Approximate Sag-Tension Calculations • Numerical Sag-Tension Calculations • Ruling Span Concept • Line Design Sag-Tension Parameters • Conductor Installation Manuel Reta-Hernández Power Delivery Consultants, Inc. Transmission Line Parameters Equivalent Circuit • Resistance • Current-Carrying Capacity (Ampacity) • Inductance and Inductive Reactance • Capacitance and Capacitive Reactance • Characteristics of Overhead Conductors Carlos V. Núñez-Noriega D.A. Douglass Insulated Power Cables for High-Voltage Applications Typical Cable Description • Overview of Electric Parameters of Underground Power Cables • Underground Layout and Construction • Testing, Troubleshooting, and Fault Location Kristine Buchholz Arizona Public Service Company Transmission Line Construction and Maintenance Tools • Equipment • Procedures • Helicopters Sherman & Reilly Pacific Gas & Electric Company Insulators and Accessories Electrical Stresses on External Insulation • Ceramic (Porcelain and Glass) Insulators • Nonceramic (Composite) Insulators • Insulator Failure Mechanism • Methods for Improving Insulator Performance Joe C. Pohlman R.G. Farmer Transmission Line Structures 4.9 Geomagnetic Disturbances and Impacts upon Power System Operation Power System Reliability Threat • Transformer Impacts Due to GIC • Magneto-Telluric Climatology and the Dynamics of a Geomagnetic Superstorm • Satellite Monitoring and Forecast Models Advance Forecast Capabilities 4.10 Lightning Protection Ground Flash Density • Stroke Incidence to Power Lines • Stroke Current Parameters • Calculation of Lightning Overvoltages on Shielded Lines • Insulation Strength • Conclusion 4.11 Reactive Power Compensation The Need for Reactive Power Compensation • Application of Shunt Capacitor Banks in Distribution Systems — A Utility Perspective • Static VAR Control (SVC) • Series Compensation • Series Capacitor Bank 4.1 Concept of Energy Transmission and Distribution George G. Karady The purpose of the electric transmission system is the interconnection of the electric energy producing power plants or generating stations with the loads. A three-phase AC system is used for most transmission lines. The operating frequency is 60 Hz in the U.S. and 50 Hz in Europe, Australia, and part of Asia. The three-phase system has three phase conductors. The system voltage is defined as the rms voltage between the conductors, also called line-to-line voltage. The voltage between the phase conductor and ground, called line-to-ground voltage, is equal to the line-to-line voltage divided by the square root of three. Figure 4.1 shows a typical system. The figure shows the Phoenix area 230-kV system, which interconnects the local power plants and the substations supplying different areas of the city. The circles are the substations and the squares are the generating stations. The system contains loops that assure that each load substation is supplied by at least two lines. This assures that the outage of a single line does not cause loss of power to any customer. For example, the Aqua Fria generating station (marked: Power plant) has three outgoing lines. Three high-voltage cables supply the Country Club Substation (marked: Substation with cables). The Pinnacle Peak Substation (marked: Substation with transmission lines) is a terminal for six transmission lines. This example shows that the substations are the node points of the electric system. The system is FIGURE 4.1 © 2001 CRC Press LLC Typical electrical system. interconnected with the neighboring systems. As an example, one line goes to Glen Canyon and the other to Cholla from the Pinnacle Peak substation. In the middle of the system, which is in a congested urban area, high-voltage cables are used. In open areas, overhead transmission lines are used. The cost per mile of overhead transmission lines is 6 to 10% less than underground cables. The major components of the electric system, the transmission lines, and cables are described briefly below. Generation Stations The generating station converts the stored energy of gas, oil, coal, nuclear fuel, or water position to electric energy. The most frequently used power plants are: Thermal Power Plant. The fuel is pulverized coal or natural gas. Older plants may use oil. The fuel is mixed with air and burned in a boiler that generates steam. The high-pressure and high-temperature steam drives the turbine, which turns the generator that converts the mechanical energy to electric energy. Nuclear Power Plant. Enriched uranium produces atomic fission that heats water and produces steam. The steam drives the turbine and generator. Hydro Power Plants. A dam increases the water level on a river, which produces fast water flow to drive a hydro-turbine. The hydro-turbine drives a generator that produces electric energy. Gas Turbine. Natural gas is mixed with air and burned. This generates a high-speed gas flow that drives the turbine, which turns the generator. Combined Cycle Power Plant. This plant contains a gas turbine that generates electricity. The exhaust from the gas turbine is high-temperature gas. The gas supplies a heat exchanger to preheat the combustion air to the boiler of a thermal power plant. This process increases the efficiency of the combined cycle power plant. The steam drives a second turbine, which drives the second generator. This two-stage operation increases the efficiency of the plant. Switchgear The safe operation of the system requires switches to open lines automatically in case of a fault, or manually when the operation requires it. Figure 4.2 shows the simplified connection diagram of a generating station. FIGURE 4.2 © 2001 CRC Press LLC Simplified connection diagram of a generating station. The generator is connected directly to the low-voltage winding of the main transformer. The transformer high-voltage winding is connected to the bus through a circuit breaker, disconnect switch, and current transformer. The generating station auxiliary power is supplied through an auxiliary transformer through a circuit breaker, disconnect switch, and current transformer. Generator circuit breakers, connected between the generator and transformer, are frequently used in Europe. These breakers have to interrupt the very large short-circuit current of the generators, which results in high cost. The high-voltage bus supplies two outgoing lines. The station is protected from lightning and switching surges by a surge arrester. Circuit breaker (CB) is a large switch that interrupts the load and fault current. Fault detection systems automatically open the CB, but it can be operated manually. Disconnect switch provides visible circuit separation and permits CB maintenance. It can be operated only when the CB is open, in no-load condition. Potential transformers (PT) and current transformers (CT) reduce the voltage to 120 V, the current to 5 A, and insulates the low-voltage circuit from the high-voltage. These quantities are used for metering and protective relays. The relays operate the appropriate CB in case of a fault. Surge arresters are used for protection against lightning and switching overvoltages. They are voltage dependent, nonlinear resistors. Control Devices In an electric system the voltage and current can be controlled. The voltage control uses parallel connected devices, while the flow or current control requires devices connected in series with the lines. Tap-changing transformers are frequently used to control the voltage. In this system, the turns-ratio of the transformer is regulated, which controls the voltage on the secondary side. The ordinary tap changer uses a mechanical switch. A thyristor-controlled tap changer has recently been introduced. A shunt capacitor connected in parallel with the system through a switch is the most frequently used voltage control method. The capacitor reduces lagging-power-factor reactive power and improves the power factor. This increases voltage and reduces current and losses. Mechanical and thyristor switches are used to insert or remove the capacitor banks. The frequently used Static Var Compensator (SVC) consists of a switched capacitor bank and a thyristor-controlled inductance. This permits continuous regulation of reactive power. The current of a line can be controlled by a capacitor connected in series with the line. The capacitor reduces the inductance between the sending and receiving points of the line. The lower inductance increases the line current if a parallel path is available. In recent years, electronically controlled series compensators have been installed in a few transmission lines. This compensator is connected in series with the line, and consists of several thyristor-controlled capacitors in series or parallel, and may include thyristor-controlled inductors. Medium- and low-voltage systems use several other electronic control devices. The last part in this section gives an outline of the electronic control of the system. Concept of Energy Transmission and Distribution Figure 4.3 shows the concept of typical energy transmission and distribution systems. The generating station produces the electric energy. The generator voltage is around 15 to 25 kV. This relatively low voltage is not appropriate for the transmission of energy over long distances. At the generating station a transformer is used to increase the voltage and reduce the current. In Fig. 4.3 the voltage is increased to 500 kV and an extra-high-voltage (EHV) line transmits the generator-produced energy to a distant substation. Such substations are located on the outskirts of large cities or in the center of several large loads. As an example, in Arizona, a 500-kV transmission line connects the Palo Verde Nuclear Station to the Kyrene and Westwing substations, which supply a large part of the city of Phoenix. © 2001 CRC Press LLC © 2001 CRC Press LLC FIGURE 4.3 Concept of electric energy transmission. The voltage is reduced at the 500 kV/220 kV EHV substation to the high-voltage level and high-voltage lines transmit the energy to high-voltage substations located within cities. At the high-voltage substation the voltage is reduced to 69 kV. Sub-transmission lines connect the high-voltage substation to many local distribution stations located within cities. Sub-transmission lines are frequently located along major streets. The voltage is reduced to 12 kV at the distribution substation. Several distribution lines emanate from each distribution substation as overhead or underground lines. Distribution lines distribute the energy along streets and alleys. Each line supplies several step-down transformers distributed along the line. The distribution transformer reduces the voltage to 230/115 V, which supplies houses, shopping centers, and other local loads. The large industrial plants and factories are supplied directly by a subtransmission line or a dedicated distribution line as shown in Fig. 4.3. The overhead transmission lines are used in open areas such as interconnections between cities or along wide roads within the city. In congested areas within cities, underground cables are used for electric energy transmission. The underground transmission system is environmentally preferable but has a significantly higher cost. In Fig. 4.3 the 12-kV line is connected to a 12-kV cable which supplies commercial or industrial customers. The figure also shows 12-kV cable networks supplying downtown areas in a large city. Most newly developed residential areas are supplied by 12-kV cables through pad-mounted step-down transformers as shown in Fig. 4.3. High-Voltage Transmission Lines High-voltage and extra-high-voltage (EHV) transmission lines interconnect power plants and loads, and form an electric network. Figure 4.4 shows a typical high-voltage and EHV system. This system contains 500-kV, 345-kV, 230-kV, and 115-kV lines. The figure also shows that the Arizona (AZ) system is interconnected with transmission systems in California, Utah, and New Mexico. These FIGURE 4.4 Typical high-voltage and EHV transmission system (Arizona Public Service, Phoenix area system). © 2001 CRC Press LLC FIGURE 4.5 Typical high-voltage transmission line. interconnections provide instantaneous help in case of lost generation in the AZ system. This also permits the export or import of energy, depending on the needs of the areas. Presently, synchronous ties (AC lines) interconnect all networks in the eastern U.S. and Canada. Synchronous ties also (AC lines) interconnect all networks in the western U.S. and Canada. Several nonsynchronous ties (DC lines) connect the East and the West. These interconnections increase the reliability of the electric supply systems. In the U.S., the nominal voltage of the high-voltage lines is between 100 kV and 230 kV. The voltage of the extra-high-voltage lines is above 230 kV and below 800 kV. The voltage of an ultra-high-voltage line is above 800 kV. The maximum length of high-voltage lines is around 200 miles. Extra-high-voltage transmission lines generally supply energy up to 400–500 miles without intermediate switching and var support. Transmission lines are terminated at the bus of a substation. The physical arrangement of most extra-high-voltage (EHV) lines is similar. Figure 4.5 shows the major components of an EHV, which are: 1. 2. 3. 4. Tower: The figure shows a lattice, steel tower. Insulator: V strings hold four bundled conductors in each phase. Conductor: Each conductor is stranded, steel reinforced aluminum cable. Foundation and grounding: Steel-reinforced concrete foundation and grounding electrodes placed in the ground. 5. Shield conductors: Two grounded shield conductors protect the phase conductors from lightning. © 2001 CRC Press LLC FIGURE 4.6 Typical 230-kV constructions. At lower voltages the appearance of lines can be improved by using more aesthetically pleasing steel tubular towers. Steel tubular towers are made out of a tapered steel tube equipped with banded arms. The arms hold the insulators and the conductors. Figure 4.6 shows typical 230-kV steel tubular and lattice double-circuit towers. Both lines carry two three-phase circuits and are built with two conductor bundles to reduce corona and radio and TV noise. Grounded shield conductors protect the phase conductors from lightning. High-Voltage DC Lines High-voltage DC lines are used to transmit large amounts of energy over long distances or through waterways. One of the best known is the Pacific HVDC Intertie, which interconnects southern California with Oregon. Another DC system is the ±400 kV Coal Creek-Dickenson lines. Another famous HVDC system is the interconnection between England and France, which uses underwater cables. In Canada, Vancouver Island is supplied through a DC cable. In an HVDC system the AC voltage is rectified and a DC line transmits the energy. At the end of the line an inverter converts the DC voltage to AC. A typical example is the Pacific HVDC Intertie that operates with ±500 kV voltage and interconnects Southern California with the hydro stations in Oregon. Figure 4.7 shows a guyed tower arrangement used on the Pacific HVDC Intertie. Four guy wires balance the lattice tower. The tower carries a pair of two-conductor bundles supported by suspension insulators. © 2001 CRC Press LLC
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.